World Products Inc., Electronic Component Solutions


About Library Distributor Login
Products Sales Reps and Distributors

Notes On Correct Use

2. Notes on Contact Load

(1)  Minimum load

If the relay is used at a voltage and current no higher than the minimum load, the contact resistance will increase and the signal may not be correctly transmitted. This happens because stabilization of the contact surface (accomplished by electrically and mechanically eliminating minute substances generated on the contact surface by opening/closing the contacts) with the minimum load probably will not occur.

In addition, even if the load is within the maximum ratings, care should be taken to ensure that the current does not drop below the minimum load ratings after opening or closing the contacts.
 

(2)  Contact protection circuit

The switching life of a relay can be improved by providing a protection circuit that suppresses transient current and voltage spikes applied to the contacts when the contacts are opened or closed.

It is important to select the correct protection circuit suitable for the contact load.
 

(A)  General notes
 
(a)  It is necessary to place the protection circuit as close to the contacts as possible. In principle, it should be placed on the same printed circuit board as that for the contacts (within a distance of several tens of centimeters).
 
(b)  It is important to confirm the effectiveness of the protection circuit in the actual circuit. In some cases, it may also be necessary to conduct life expectancy tests using an appropriate equivalent circuit.
 
(B)  Examples of contact protection circuits
 
(a)  Inductive load

With an inductive load, when the contacts are opened to break the circuit, a counter electromotive force as shown in Fig. 1 is generated, causing an electric discharge between the contacts. This discharge energy accelerates metal dislocation and wear on the contact surface. A protection circuit is therefore necessary to absorb this counter electromotive force. Table 1 shows guideline circuit examples and circuit constants. Never use a connection with a capacitor only as shown in Table 2.
 

Fig. 1 Inductive Load Circuit

Table 1 Inductive Load Contact Protection Circuits

Protection element Circuit example Remarks
Capacitor
+
Resistor
(CR circuit)
r(ohm) = contact voltage (V)

0.5 to1
C (µF) = (0.5 to 1) x contact current (A)

The breakdown voltage of a non-polar capacitor should be 300 V or higher.

Varistor
High voltage is suppressed by using the voltage characteristics of the varistor.
Diode
Pay attention to the reverse breakdown voltage of the diode.
Diode
+
Zener Diode
The ON time of the diode is controlled by using the Zener voltage characteristic and the recovery time of the relay can be shortened.

Table 2 Examples of Wrong Circuits Using Capacitors

WRONG
This circuit is effective for arc suppression when the contacts are opened, but when the contacts are closed a capacitor short-circuit current flows, making the contacts more susceptible to metal deposition. WRONG
This circuit is effective for arc suppression when the contacts are opened, but when the contacts are closed a capacitor charging current flows, making the contacts more susceptible to metal deposition.

      (b)  Lamp loads (inrush current), etc.

Some loads, such as halogen lamps, have a low initial resistance so that an inrush current 10 times as high as the steady-state current may flow through the relay on power application. A high inrush current may also flow when the relay is used to switch loads such as motors and capacitors. In these cases, a current-limiting resistor may be connected in series with the contacts to keep the inrush current limited (refer to Fig. 2).
 

Fig. 2 Example of Current-Limiting Resistor in Lamp Load Circuit

     (c)  Stray line capacitance

When the stray line capacitance is large, the inrush current that is generated from it may pose a problem. As shown in Fig. 3, the electric charge of the line capacitance is discharged directly through the contacts when the contacts are closed. The smaller the characteristic cable impedance and the longer the cable, the greater wear on the contacts.

It may be necessary to connect a current-limiting resistor or surge suppressor in series with the contacts as a protection circuit.
 

Fig. 3 Example of Surge Suppression Circuit with Surge Suppressor

Back to: 1. General
Forward to:  3. Notes on Driving Relays
4. Notes on Operating Environments
5. Influence of Relay Operation on Surroundings
6. Notes on Mounting
7. Notes on Cleaning
8. Notes on Handling Relays
9. Notes on Using SMT Relays

Home

© 2013 World Products Inc. All rights reserved. Disclaimer.
Last updated: 10-1-00